How to prevent acetylene in transformer oil?

Writer: Kaiqian Oil Purifier Release time:2022-03-01 16:12 Clicks:

1. Before the transformer oil is put into storage, the oil must be tested to ensure that there is no acetylene, and then the sample shall be reserved and received.

2. The transformer manufacturer should regularly conduct chromatographic analysis on the oil used to flush the transformer accessories. Once acetylene is found, it should not be used again without treatment

3. Before installation, in addition to chromatographic analysis of transformer body oil and make-up oil, spot check the residual oil in accessories or flush Fujian if necessary


4. After the transformer accessories are installed and the accessory oil is replenished, the oil sample shall be taken after standing for a period of time

5. Arrange a meteorological chromatographic analysis after the voltage withstand test or before and after the partial discharge test

6. Strengthen the factory supervision of transformer equipment, especially the quality Star Management of off-site purchased parts of transformer.

7. The residual oil in the body shall be drained before oil filling. All work shall be filled with vacuum oil filter. The oil filling shall be stable and the speed shall be ≤ 100lmin. The hot oil circulation shall be carried out after oil filling, and the air shall be deflated regularly during hot oil circulation

8. Before each oil filtration, the oil filter, oil pipe and other relevant equipment shall be completely cleaned. When filtering oil, professional transformer oil vacuum filter is used to prevent mixing with other miscellaneous oil, so as to cut off the secondary pollution source of transformer oil.

9. Regularly maintain or inspect the oil filter to ensure the normal operation of the oil pump.

10. After welding with oil, gas chromatography must be carried out. If acetylene is found, use vacuum oil filter to purify transformer lubricating oil in time.

11. Regularly check the insulation of the heater to prevent damage to the heater λ function. The warm cooking regulator should be controlled at 50-60 ° C

12. When not in use, the welding gas should be placed in the specified gas storage room to prevent leakage and pollution of transformer oil.

If acetylene gas is found in the transformer oil, the vacuum degassing method is generally used to remove acetylene. If only the circulation in the transformer body is adopted, some acetylene gas will be adsorbed in the blind area of the transformer body or transformer tank.